Product Overview
The SI-100 is a fixed gas detection system designed for reliable monitoring of combustible gases, toxic gases, and oxygen in industrial environments. It provides accurate, real-time detection with visual, audible, and relay-based alerts, and supports RS-485 digital communication for integration into control systems.
- Multi-Gas Detection: Monitors combustible, toxic, and oxygen levels.
- Reliable Sensors: Long-life catalytic, IR, electrochemical, and galvanic sensors.
- Fast Response: Rapid detection with response times under 30 seconds.
- User-Friendly Operation: Non-intrusive input via magnetic wand and optional RS-485 interface.
- Robust Design: Aluminum transmitter and stainless steel sensor housing with IP-rated protection.
- Flexible Integration: Supports relay, analog, and digital outputs for control systems.
- Certifications: Explosion-proof approvals including KCs, IECEx, and INMETRO.
Feature | Details |
---|---|
Model Name | SI-100 |
Detected Gas | Combustible Gas, Toxic Gas, Oxygen |
Detection Principle | Catalytic, IR, Electrochemical Cell, Galvanic |
Sensor Life | >5 years (Combustible), >2 years (Toxic), <2 years (Oxygen) |
Response Time | <15 sec (90% scale Combustible), <30 sec (90% scale IR), <15 sec (O₂) |
Resolution | 1%LEL (Combustible), 0.1%VOL (O₂) |
Detection Type | Diffusion Type |
Accuracy | ±3% Full Scale |
Operating Voltage | 18~32Vdc |
Power Consumption | 2.8W @ 24Vdc |
Indicators | FND, Gas Concentration, Alarm, Device Fault |
Relay Output | 1st Alarm, 2nd Alarm, Fault Alarm (Rated 5.0A @30Vdc) |
Analog Output | 4~20mA (HART: Optional) |
Digital Communication | RS-485 |
Remote Interface | RS-485 Modbus, HART (Optional) |
Input & Setting | Non-Intrusive with Magnetic Wand & RS-485 (Optional) |
Wiring | 4~20mA / DC / Relay: Max 20 AWG |
Operating Temperature | -20℃ ~ +55℃ |
Operating Humidity | 5% ~ 95% RH (Non-condensing) |
Conduit Size | 3/4” NPT × 2EA |
Device Warranty | 2 Years |
Sensor Warranty | 1 Year |
Material | Transmitter: Aluminum, Sensor Housing: Stainless Steel (SS316) |
Dimensions | 150(W) x 165(H) x 110(D) mm |
Weight | Approx. 1.9kg |
Explosion-proof Certification | KCs: Ex d IIC T5, IECEx: Ex d IIC T5, INMETRO: Ex db IIC T5 Gb |
Gas | Sensor | Range | Low Alarm | High Alarm | Resolution |
---|---|---|---|---|---|
O₂ | Electrochemical | 0~30%vol | 19.0%vol | 23.0%vol | 0.1%vol |
CO | Electrochemical | 0~500ppm | 30ppm | 60ppm | 1ppm |
SO₂ | Electrochemical | 0~20ppm | 2ppm | 5ppm | 0.1ppm |
H₂ | Catalytic | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
H₂ | Electrochemical | 0~1,000ppm | 100ppm | 500ppm | 5ppm |
H₂S | Electrochemical | 0~500ppm | 10ppm | 15ppm | 1ppm |
Combustible | Catalytic | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
Combustible | IR | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
NH₃ | Electrochemical | 0~100ppm | 25ppm | 35ppm | 1ppm |
C₂H₂ | Catalytic | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
C₂H₄O | Catalytic | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
C₆H₆ | IR | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
C₇H₈ | Catalytic | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
CH₄ | IR | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
CH₄ | Catalytic | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
Cl₂ | Electrochemical | 0~5ppm | 0.5ppm | 1.0ppm | 0.1ppm |
Cl₂ | Electrochemical | 0~20ppm | 0.5ppm | 1.0ppm | 0.1ppm |
CO₂ | IR | 0~2,000ppm | 1,000ppm | 1,500ppm | 3ppm |
CO₂ | IR | 0~5,000ppm | 3,000ppm | 5,000ppm | 8ppm |
CO₂ | IR | 0~5%vol | 0.5%vol | 3%vol | 0.1%vol |
HCl | Electrochemical | 0~10ppm | 1ppm | 2ppm | 0.1ppm |
VOC | PID | 0~1,000ppm | 50ppm | 100ppm | within 3ppm |
C₈H₁₀ | Catalytic | 0~100%LEL | 15%LEL | 50%LEL | 1%LEL |
H₂O₂ | Electrochemical | 0~10ppm | 1ppm | 2ppm | 0.1ppm |
NO₂ | Electrochemical | 0~20ppm | 3ppm | 5ppm | 0.1ppm |
C₂H₄O | Electrochemical | 0~30ppm | 1ppm | 2ppm | 0.1ppm |
NO | Electrochemical | 0~100ppm | 25ppm | 50ppm | 1ppm |
HF | Electrochemical | 0~5ppm | 0.5ppm | 1ppm | 0.1ppm |