Description
The OTIS OI-660 is an ultraviolet flame detector for hazardous areas where fire has to be caught fast — turbine enclosures, generator rooms, battery rooms, gas cabinets, and munitions facilities. UV sensing picks up both hydrocarbon flames (gasoline, propane, methane, alcohol) and non-hydrocarbon flames (hydrogen, silane, hydrazine) that IR-only detectors can miss, and the built-in automatic self-test continuously proves the detector can still see fire — reporting a fault if its view is impaired.
It wires into whatever your fire panel speaks: two user-configurable relays (fire/trouble, latching or non-latching), a 0–20 mA loop, and programmable RS-485 Modbus. The explosion-proof enclosure carries Class I Division 1 and Class II Division 1 ratings plus NEMA 4X and ATEX/IECEx, with a high-temperature version available to +125 °C for turbine enclosures. Aim it exactly where the hazard is with the OI-208 swivel bracket in aluminum or stainless.
- Ultraviolet sensing — catches hydrocarbon and non-hydrocarbon flames (hydrogen, silane, hydrazine)
- Fast response: certified to catch a 1 sq ft gasoline flame at 50 ft within 1 second; 120° field of view
- Automatic through-the-lens self-test — continuously verifies fire-sensing ability, reports fault when impaired
- Two user-configurable relays (fire/trouble, NO/NC, latching or non-latching) + 0–20 mA + RS-485 Modbus
- Explosion-proof: Class I Div 1 Groups B, C, D; Class II Div 1 Groups E, F, G; NEMA 4X; ATEX/IECEx
- High-temperature version available to +125 °C for turbine enclosures
- Pairs with the OI-208 swivel bracket (aluminum or stainless) for precise aiming
| OTIS model | 660-00100 |
|---|---|
| Sensing | Ultraviolet, peak sensitivity 0.22 µm |
| Power | 24 VDC nominal (20–32 VDC) |
| Outputs | 2 relays (fire/trouble, dry contact, 2 A @ 28 VDC, NO/NC, latching/non-latching selectable); 0–20 mA (20 = fire, 4 = ready); programmable RS-485 Modbus |
| Temperature | -40 to +85 °C standard; high-temp version to +125 °C |
| Certifications | Class I Div 1 Groups B, C, D; Class II Div 1 Groups E, F, G; NEMA 4X; ATEX/IECEx |
| Housing | Copper-free aluminum (white) standard, stainless steel optional; 4.5 in H x 5.5 in W x 6 in D; 5 lbs aluminum / 13 lbs stainless |
| Conduit entry | 3/4-14 NPTF or M20-1.5 |
| Accessories | OI-208 swivel bracket (aluminum / stainless), portable test unit, air shield kit |
| Warranty | 1-year limited hardware |