Blog
Bump Testing a Pumped Detector: Sample-Draw Mistakes That Fail Good Meters
A pumped gas detector is only truly bump tested when the test gas travels the whole sample path — in at the probe tip, through the full hose and both filter stacks — and is given draw time plus the sensor's T90 to arrive; on the RKI GX-Force that means allowing for a sample draw of up to 100 feet on top of a specified T90 within 30 seconds. Bump at the case, pull the gas off early, or test through a wet or clogged filter, and the test fails good meters — or worse, passes a sample path that canno
…
Nov 10th 2026
Pumped Detector Filters: The Cheap Part That Decides Your Readings
Every reading from a pumped gas detector passes through its filters before it reaches a sensor — on the RKI GX-Force, a hydrophobic membrane and wire-mesh disk at the inlet and a particle filter over a second hydrophobic disk inside the probe. When those disks clog with dust or saturate with liquid, the pump starves: readings arrive low and late, response stretches past the GX-Force's specified T90 of 30 seconds, the pump strains and trips low-flow alarms — and the sensors, which are usually hea
…
Nov 9th 2026
What Should You Do When Your Gas Detector Gets Wet?
Take a gas detector that has been soaked or immersed out of service immediately, and do not trust its readings until it is completely dry, its hydrophobic filter has been inspected or replaced, and it has passed a bump test and a full calibration. An IP67 rating certifies only temporary immersion in clean water — 1 metre for 30 minutes — and SENKO states in its own manual that an IP rating does not imply the equipment will detect gas during or after exposure to those conditions.
It happens on or
…
Nov 8th 2026
How Do You Store a Gas Detector Between Jobs?
Store a gas detector between jobs indoors at normal temperature and humidity, out of direct sunlight and away from gases, solvents, vapors, and dust — and put it away with the battery run down, not full: RKI's GX-3R manual instructs users to discharge the battery to 1 bar on the battery icon for storage, to prolong battery life and prevent battery deterioration. Storage does not pause the meter's clocks — the oxygen sensor keeps consuming itself in room air and the battery keeps draining while t
…
Nov 7th 2026
Fixed Gas Detector Alarm Setpoints: Who Decides, and What Do They Set?
Fixed gas detector alarm setpoints are decided by the facility — not by OSHA, and not by the factory default alone — using exposure limits and fire risk: combustible gas typically alarms at 10% LEL low and 20% LEL high, oxygen at 19.5% low and 23.5% high, hydrogen sulfide at 10 ppm low and 15 ppm high, and carbon monoxide at 35 ppm low and 200 ppm high. Each tier needs a named action — investigate and ventilate at the low alarm, evacuate and shut down at the high alarm — or the setpoint is just
…
Nov 6th 2026