How Do You Read a Calibration Gas Certificate of Analysis?
You read a calibration gas Certificate of Analysis (CoA) by matching the cylinder in your hand to the certificate line by line: the lot number must match, and you calibrate to each component's certified (actual) concentration — not the nominal concentration the blend was ordered at. Finish with the dates and the traceability statement: the expiry date must be in the future, and the certificate should state what its values are traceable to — on CPS's ISG cylinders the gas is NIST-trac
…
Oct 20th 2026
What Gases Do You Monitor in a Parking Garage? CO and NO₂ Fixed Detection Explained
In an enclosed parking garage you monitor two gases: carbon monoxide (CO), produced mainly by gasoline engines, and nitrogen dioxide (NO₂), the marker gas for diesel exhaust. The International Mechanical Code's ventilation model for enclosed garages (Section 404 in recent editions) runs the exhaust system automatically from CO and NO₂ detectors working together — full ventilation at not less than 0.75 cfm per square foot of floor area, dropping to a standby rate of not less than 0.05 cfm p
…
Oct 20th 2026
Why Do Battery Rooms Need Hydrogen Detection? H₂ Monitoring for Charging Areas
Charging lead-acid batteries vents hydrogen gas, and hydrogen ignites at just 4% by volume in air — its lower explosive limit (LEL). The fire codes written for battery rooms (IFC Section 608 and NFPA 1 Chapter 52) require ventilation designed to hold hydrogen at or below 1% of the room's volume, which is exactly 25% of that LEL — and a hydrogen detector, mounted at the room's highest point and typically alarming at 10% of LEL (0.4% vol), is how a facility proves the ventilation is wo
…
Oct 20th 2026
Chlorine Gas Detection in Water Treatment: Where Chlorine Hides and How It's Monitored
Chlorine gas is about 2.5 times as dense as air, so a leak sinks and pools at floor level — and the exposure limits leave almost no room above the alarm point: OSHA's ceiling is 1 ppm, never to be exceeded at any time; NIOSH's recommended ceiling is 0.5 ppm over 15 minutes; and 10 ppm is immediately dangerous to life or health (IDLH). That is why chlorine storage rooms, chlorinator rooms and scrubber spaces get low-mounted fixed detectors wired to ventilation and alarms outside the room &m
…
Oct 20th 2026
Gas Detection for Hot Work: What Does a Fire Watch Need to Monitor?
A fire watch monitors fire — but the atmosphere has to be proven safe before hot work starts and watched while it burns, and that is a gas detector's measurement, not an eye's. The monitoring is the standard confined-space four: combustible gas held below 10% of the lower explosive limit, oxygen in the safe band, and carbon monoxide and hydrogen sulfide in range when the work sits next to a process area, tank, sewer or pit. A pumped multi-gas monitor tests the space before anyone strikes a
…
Oct 20th 2026