Blog
Chlorine Gas Detection in Water Treatment: Where Chlorine Hides and How It's Monitored
Chlorine gas is about 2.5 times as dense as air, so a leak sinks and pools at floor level — and the exposure limits leave almost no room above the alarm point: OSHA's ceiling is 1 ppm, never to be exceeded at any time; NIOSH's recommended ceiling is 0.5 ppm over 15 minutes; and 10 ppm is immediately dangerous to life or health (IDLH). That is why chlorine storage rooms, chlorinator rooms and scrubber spaces get low-mounted fixed detectors wired to ventilation and alarms outside the room &m
…
Oct 20th 2026
Gas Detection for Hot Work: What Does a Fire Watch Need to Monitor?
A fire watch monitors fire — but the atmosphere has to be proven safe before hot work starts and watched while it burns, and that is a gas detector's measurement, not an eye's. The monitoring is the standard confined-space four: combustible gas held below 10% of the lower explosive limit, oxygen in the safe band, and carbon monoxide and hydrogen sulfide in range when the work sits next to a process area, tank, sewer or pit. A pumped multi-gas monitor tests the space before anyone strikes a
…
Oct 20th 2026
Landfill and Biogas Gas Monitoring: Methane, H₂S, and Oxygen Together
Landfill gas is roughly 50% methane and 50% carbon dioxide (EPA's Landfill Methane Outreach Program figure), and digester biogas runs 50–75% methane — concentrations thousands of times higher than a %LEL sensor is built to read, which is why landfill and biogas monitoring measures methane in % volume with infrared or thermal-conductivity sensors. Around those percentages sits the rest of the trio: hydrogen sulfide, from trace odor levels in landfill gas to thousands of ppm in raw bio
…
Oct 20th 2026
What Are Gas Detection Tubes and When Do You Use Them Instead of a Monitor?
A gas detection tube is a sealed glass tube filled with a chemical reagent that changes color when a measured sample of air is drawn through it with a hand pump — the length of the resulting color stain, read against the scale printed on the tube, is the gas concentration. Each tube measures one gas, exactly once, with no battery, no calibration, and no electronics; at CPS the system is NAGCO's, with the PP-2025 hand pump kit at $395 and standard tube boxes at $49–$59.
Detector tubes
…
Oct 20th 2026
Can a Thermal Imaging Camera See a Gas Leak?
A standard thermal imaging camera cannot see a gas leak — it images surface temperatures, and methane, propane, and most other industrial gases are transparent in the infrared band it uses. The exception is optical gas imaging (OGI): a thermal camera fitted with a spectral filter tuned to the narrow infrared band a specific gas absorbs, which makes the escaping gas visible as a plume. At CPS the OGI cameras are FLIR's uncooled GF77 ($37,950, with interchangeable lenses covering hydrocarbon
…
Oct 20th 2026